Quantity: RF voltage and current: RF voltage meters
Internal identifier Range Calibration and measurement capabilities Conditions of measurement Procedure Note to procedure
RF34 (0.1 - 7) V (4,5 - 15) mV/V
  • frequency 0 GHz to 2 GHz
  • connector 50 Ω
113-MP-C010, 113-MP-C011
RF34 (0.1 - 7) V (4,5 - 15) mV/V
  • frequency 0 GHz to 2 GHz
  • connector 50 Ω
113-MP-C010, 113-MP-C011
Quantity: voltage
Internal identifier Range Calibration and measurement capabilities Conditions of measurement Procedure Note to procedure
9.27 (0.01 - 10) V (1.5 - 1.5) % MH
  • frequency 0,1 MHz up to 2 GHz
113-MP-C014
Quantity: vertical deflection factor
Internal identifier Range Calibration and measurement capabilities Conditions of measurement Procedure Note to procedure
9.22 (1 - 21) mV (0,1% MH + 15mV - 0,1% MH + 15mV)
  • frequency 10 Hz up to 10 kHz
113-MP-C008
9.22 (21 - 556) mV (0,1% MH + 1mV - 0,1% MH + 1mV)
  • frequency 10 Hz up to 10 kHz
113-MP-C008
9.22 (0.556 - 210) V (0,05% MH + 1mV - 0,05% MH + 1mV)
  • frequency 10 Hz up to 10 kHz
113-MP-C008
Quantity: time base
Internal identifier Range Calibration and measurement capabilities Procedure Note to procedure
9.23 (1.0E-9 - 50) s (2.5E-7 - 2.5E-7) 113-MP-C008
Quantity: bandwidth
Internal identifier Range Calibration and measurement capabilities Procedure Note to procedure
9.24 (0 - 100) MHz (3 - 3) % 113-MP-C008
9.24 (0 - 550) MHz (6 - 6) % 113-MP-C008
9.24 (0 - 1.1) GHz (8 - 8) % 113-MP-C008
Quantity: rise time
Internal identifier Range Calibration and measurement capabilities Procedure Note to procedure
9.25 (300 - 300) ps (12 - 12) ps 113-MP-C008
Quantity: hf power: power sensor calibration factor
Internal identifier Range Calibration and measurement capabilities Conditions of measurement Procedure Note to procedure
9.26 (0.05 - 1.1) (0.9 - 0.9) %MH
  • frequency 0 GHz up to 1 GHz
113-MP-C014
9.26 (0.05 - 1.1) (1.5 - 1.5) %MH
  • frequency 1 GHz up to 18 GHz
113-MP-C014
9.26 (0.05 - 1.1) (2 - 2) %MH
  • frequency 18 GHz up to 40 GHz
113-MP-C014
Quantity: hf power
Internal identifier Range Calibration and measurement capabilities Conditions of measurement Procedure Note to procedure
9.26 (-100 - -50) dBm (0,19-0,0012 (MH+50) - 0,19-0,0012 (MH+50)) dB
  • frequency 0,1 MHz up to 4,2 GHz
113-MP-C014
9.26 (-50 - 20) dBm (0.1 - 0.1) dB
  • frequency 0,1 MHz up to 4,2 GHz
113-MP-C014
9.26 (-100 - -50) dBm (0,29-0,005 (MH+50) - 0,29-0,005 (MH+50)) dB
  • frequency 4,2 GHz up to 18 GHz
113-MP-C014
9.26 (-50 - 20) dBm (0.15 - 0.15) dB
  • frequency 4,2 GHz up to 18 GHz
113-MP-C014
9.26 (-90 - -50) dBm (0,44-0,0027 (MH+50) - 0,44-0,0027 (MH+50)) dB
  • frequency 18 GHz up to 26,5 GHz
113-MP-C014
9.26 (-50 - 20) dBm (0.15 - 0.15) dB
  • frequency 18 GHz up to 40 GHz
113-MP-C014
9.26 (20 - 43) dBm (0.17 - 0.17) dB
  • frequency 0,01 GHz up to 18 GHz
113-MP-C014
9.26 (43 - 53) dBm (0.17 - 0.17) dB
  • frequency 0,01 GHz up to 1 GHz
113-MP-C014
9.28 (20 - -20) dBm (0.17 - 0.17) dB
  • frequency 0,1 MHz up to 6 GHz
113-MP-C014
9.28 (-20 - -60) dBm (0.22 - 0.22) dB
  • frequency 0,1 MHz up to 6 GHz
113-MP-C014
Quantity: hf power ratio (attenuation, gain)
Internal identifier Range Calibration and measurement capabilities Conditions of measurement Procedure Note to procedure
9.26 (0 - 55) dB (0,015+0,0005 MH - 0,015+0,0005 MH) dB
  • frequency 0,1 MHz up to 26,5 GHz
113-MP-C014
9.26 (55 - 75) dB (0,046+0,0005 MH - 0,046+0,0005 MH) dB
  • frequency 0,1 MHz up to 26,5 GHz
113-MP-C014
9.26 (75 - 90) dB (0,12+0,0047 (MH-75) - 0,12+0,0047 (MH-75)) dB
  • frequency 0,1 MHz up to 18 GHz
113-MP-C014
9.26 (75 - 90) dB (0,12+0,019 (MH-75) - 0,12+0,019 (MH-75)) dB
  • frequency 18 GHz up to 26,5 GHz
113-MP-C014
9.26 (90 - 100) dB (0,12+0,012 (MH-90) - 0,12+0,012 (MH-90)) dB
  • frequency 0,1 MHz up to 13,2 GHz
113-MP-C014
9.26 (0 - 40) dB (0.1 - 0.1) dB
  • frequency 26,5 GHz up to 40 GHz
113-MP-C014
Quantity: antenna factor
Internal identifier Range Calibration and measurement capabilities Conditions of measurement Procedure Note to procedure
(-60 - 90) dB (0.14 - 1) dB
  • frequency 10 Hz to 30 MHz
113-MP-C016
Field of measurement: time and frequency
Quantity: frequency
Internal identifier Range Calibration and measurement capabilities Procedure Note to procedure
1 (0.01 - 3.0E+9) Hz (1.0E-11 - 1.0E-11) 113-MP-C007
1 (3 - 18) GHz (1.0E-11 - 1.0E-11) 113-MP-C007
1 (18 - 46) GHz (3 - 3) Hz 113-MP-C007
Quantity: period
Internal identifier Range Calibration and measurement capabilities Procedure Note to procedure
2 (5.0E-9 - 1.0E+5) s (1.0E-11 - 1.0E-11) 113-MP-C007
Quantity: time interval
Internal identifier Range Calibration and measurement capabilities Procedure Note to procedure
3 (0 - 1.0E+5) s (1,1×10-9 + 1×10-11 t - 1,1×10-9 + 1×10-11 t) s 113-MP-C007
3 (0 - 10) s (10×10-12 + 2×10-3 t - 10×10-12 + 2×10-3 t ) s 113-MP-C007
Quantity: pulse counting
Internal identifier Range Calibration and measurement capabilities Conditions of measurement Procedure Note to procedure
4 (0 - 1.0E+7) s 0
  • fmax=50 MHz 
113-MP-C007
Quantity: frequency deviation of frequency modulation
Internal identifier Range Calibration and measurement capabilities Conditions of measurement Procedure Note to procedure
5 (0.2 - 40) kHz (1.5 - 1.5) %
  • fc=250 kHz up to 10 MHz, fmod: 20 Hz up to 10 kHz, Df/fmod ˃ 0,2 
113-MP-C007
5 (0.2 - 40) kHz (1 - 1) %
  • Df/fmod ˃ 1,2 
113-MP-C007
5 (0.25 - 400) kHz (1.5 - 1.5) %
  • fc=10 MHz up to 6,6 GHz, fmod: 50 Hz up to 200 kHz, Df/fmod ˃ 0,2 
113-MP-C007
5 (0.25 - 400) kHz (1 - 1) %
  • Df/fmod ˃ 0,45 
113-MP-C007
Field of measurement: metrology in chemistry
Quantity: Concentration
Internal identifier Range Calibration and measurement capabilities Analyt nebo komponenta Matrice Procedure Note to procedure
0.14 - 0.14 mg.l-1 0.006 - 0.006mg.l-1 ethanol in the gas phase 114-MP-C004
0.48 - 0.48 mg.l-1 0.011 - 0.011mg.l-1 ethanol in the gas phase 114-MP-C004
0.9 - 0.9 mg.l-1 0.019 - 0.019mg.l-1 ethanol in the gas phase 114-MP-C004
1.4 - 1.4 mg.l-1 0.028 - 0.028mg.l-1 ethanol in the gas phase 114-MP-C004
0.14 - 0.14 mg.l-1 0.008 - 0.008mg.l-1 ethanol in the gas phase 114-MP-C004
Field of measurement: ionising radiation
Quantity: Activity per unit area (C-14)
Internal identifier Range Calibration and measurement capabilities Conditions of measurement Procedure Note to procedure
EUR-RAD-CMI-2001 (1 - 100) Bq.cm-2 3.6 %
  • C-14 rectangular, 110 mm x 150 mm, or circular, diameter 23 mm to 45 mm
115-MP-C007
Quantity: Activity per unit area (Co-60)
Internal identifier Range Calibration and measurement capabilities Conditions of measurement Procedure Note to procedure
EUR-RAD-CMI-2002 (10 - 100) Bq.cm-2 3.2 %
  • Co-60 rectangular, 110 mm x 150 mm, or circular, diameter 23 mm to 45 mm
115-MP-C007
Quantity: Activity per unit area (Sr-90)
Internal identifier Range Calibration and measurement capabilities Conditions of measurement Procedure Note to procedure
EUR-RAD-CMI-2003 (10 - 100) Bq.cm-2 3.2 %
  • Sr-90 rectangular, 110 mm x 150 mm, or circular, diameter 23 mm to 45 mm